• Best quality
  • Quick assembly
  • Longevity

HeatBloC®

Heating

technology

Distribution manifold DN 50 (2")

Modular design,
for outputs up to 400 kW (for each boiler connection) at a temperature difference of 20 K

SKU
511x
Prices are only visible for registered users.

Our offer is exclusively aimed at corporate clients.

Manufacturer:
PAW GmbH & Co. KG
Böcklerstr. 11 31789 Hameln
Germany
info@paw.eu
Operating data
Max. operating temperature: 110 °C
Output: 400 kW
Max. operating pressure: 6 bar
Temperature difference: 20 K
Kvs value modular distribution manifold: 4-fold: 86,3-fold: 75,2-fold: 70
Dimensions
Height: 225 mm
Nominal diameter: DN 50 (2")
Connection generator: Flange DN 65 / PN 6, flow at the side, return to the bottom, others sealed with 2" plug
Connection consumer: Flange DN 50 / PN 6 (on top)
Lateral connection: 1¼" int. thread, sealed with plug, for safety group and expansion tank
Centre distance: 180 mm
Height insulation: 220 mm
Materials
Valves and fittings: Brass
Gaskets: EPDM / AFM34
Insulation: EPP
modular distribution manifold made of brass
connecting flanges as slip-on flanges made of steel
gaskets and screws for boiler connection DN 65 included
completely premounted
entirely insulated with EPP shells
extremely low resistance, free passage d = 84 mm
up to 4 groups, premounted, extendable
boiler connections DN 65

Safety instructions
The installation and commissioning as well as the connection of electrical components require technical knowledge commensurate with a recognised vocational qualification as a fitter for plumbing, heating and air conditioning technology, or a profession requiring a comparable level of knowledge [specialist].
The following must be observed during installation and commissioning:
- relevant local and national regulations
- accident prevention regulations of the professional association
- instructions and safety instructions mentioned in these instructions.

CAUTION
Personal injury and damage to property!
The product must only be used in heating circuits filled with heating water according to VDI 2035 / Ö-Norm H 5195-1. The product must not be used in domestic water applications.

NOTICE
Material damage due to mineral oils!
Mineral oil products cause lasting damage to seals made of EPDM, whereby the sealant properties get lost. We do not assume liability nor provide warranty for damage to property resulting from sealants damaged in this way.
- It is imperative to avoid that the EPDM sealing elements of the unit get in contact with substances containing mineral oils.
- Use a lubricant based on silicone or polyalkylene and free from mineral oils, such as Unisilikon L250L and Syntheso Glep 1 of the Klüber company or a silicone spray.