• Best quality
  • Quick assembly
  • Longevity

HeatBloC®

Heating

technology

HeatBloC® MC43 - DN 40 (1½")

3-way mixing valve with integrated bypass 0-50 %
with integrated controller
Application range: for radiant floor heating from 3.5 kW, for low-temperature heating systems controlled by a mixing valve
Recommended application range:up to 125 kW; 20 K up to 5400 l/h

SKU
4541071M
Prices are only visible for registered users.

Our offer is exclusively aimed at corporate clients.

Manufacturer:
PAW GmbH & Co. KG
Böcklerstr. 11 31789 Hameln
Germany
info@paw.eu
Operating data
Max. operating temperature: 110 °C
Differential pressure sensors: 0-600 mbar
Dial thermometer: 0 - 120 °C
Output: 125 kW
Max. operating pressure: 6 bar
Temperature difference: 20 K
Kvs value: 17.7
Flow rate: 5400 l/h
Power consumption: 1.5 W
Equipment
Controller MCom 3.4: 24 Vdc, max. 200 mA Interface: Modbus RTU (integration into building control and SmartHome systems )
Check valves: 1 x 250 mm wc
Dial thermometer: 0 - 120 °C
Shut-off valves: Ball valves with handle
Temperature sensors: 1x Pt1000 in the flow and return
Differential pressure sensors: 0-600 mbar
Opening pressure check valve: 250 mm wc
Number of check valves: 1
Dimensions
Height: 790 mm
Width: 320 mm
Nominal diameter: DN 40 (1½")
Installation length: 560 mm
Connection generator: Flange DN 40 / PN 6
Connection consumer: 1½" int. thread
Centre distance: 160 mm
Materials
Valves and fittings: Brass
Gaskets: EPDM
Insulation: EPP
Electrical data (heating/actuators)
Setting time 90°: 140 s
Electrical connection: 24 V AC/DC
Torque actuator: 10 Nm
Power consumption: 1.5 W
EnEV-compliant hydraulic balancing on the distribution manifold ...

Safety instructions
The installation and commissioning as well as the connection of electrical components require technical knowledge commensurate with a recognised vocational qualification as a fitter for plumbing, heating and air conditioning technology, or a profession requiring a comparable level of knowledge [specialist].
The following must be observed during installation and commissioning:
- relevant local and national regulations
- accident prevention regulations of the professional association
- instructions and safety instructions mentioned in these instructions.

CAUTION
Personal injury and damage to property!
The product must only be used in heating circuits filled with heating water according to VDI 2035 / Ö-Norm H 5195-1. The product must not be used in domestic water applications.

NOTICE
Material damage due to mineral oils!
Mineral oil products cause lasting damage to seals made of EPDM, whereby the sealant properties get lost. We do not assume liability nor provide warranty for damage to property resulting from sealants damaged in this way.
- It is imperative to avoid that the EPDM sealing elements of the unit get in contact with substances containing mineral oils.
- Use a lubricant based on silicone or polyalkylene and free from mineral oils, such as Unisilikon L250L and Syntheso Glep 1 of the Klüber company or a silicone spray.