• Best quality
  • Quick assembly
  • Longevity

HeatBloC®

Heating

technology

HeatBloC® K31 DN 25 (1")

direct / unmixed
Field of application: for boiler charging, for modulating temperature heating
Recommended application range: up to 50 kW; 20 K up to 2150 l/h

SKU
36013xx
Prices are only visible for registered users.

Our offer is exclusively aimed at corporate clients.

Manufacturer:
PAW GmbH & Co. KG
Böcklerstr. 11 31789 Hameln
Germany
info@paw.eu
Operating data
Max. operating temperature: 110 °C
Dial thermometer: 0 - 120 °C
Output: 50 kW
Max. operating pressure: 6 bar
Temperature difference: 20 K
Kvs value: 7.2
Flow rate: 2150 l/h
Equipment
Check valves: 1 x 200 mm wc
Dial thermometer: 0 - 120 °C
Shut-off valves: Ball valves with handle
Opening pressure check valve: 200 mm wc
Number of check valves: 1
Dimensions
Height: 383 mm
Width: 250 mm
Nominal diameter: DN 25 (1")
Installation length: 340 mm
Connection generator: 1½" ext. thread, flat sealing
Connection consumer: 1" int. thread
Centre distance: 125 mm
Materials
Valves and fittings: Brass
Gaskets: EPDM
Insulation: EPP
Flat-sealing connections 1½" ext. thread
incl. 1½" union nut for the installation on a PAW modular distribution manifold.
With PAW mounting equipment the heating circuit can be installed on wall brackets.

Large ball valve handles,
easy handling, visible closing position

EnEV-compliant functional insulation
made of durable elastic EPP, complete insulation of valves and fittings, ventilation opening to cool the pump

Free access to the pump head
by simply removing the front insulation shell

Check valve in the return pipe
can be opened, 200 mm wc, spring-loaded, thus suited for horizontal and overhead installation

Flow on the right = standard
Flow and return line can be changed on site, also for heating circuits with mixing valve

Full metal thermometers
can be pulled off, with immersion sleeve integrated in the ball valve

PAW heating pumps with high-efficiency (ECM) technology
fitted with 2 m cable, completely premounted, integrated in the insulation, pressure tested, with serial number, perfectly designed system, pump characteristics, EuP/ErP READY

Pump can be isolated,
so that it can be replaced without draining

Safety instructions
The installation and commissioning as well as the connection of electrical components require technical knowledge commensurate with a recognised vocational qualification as a fitter for plumbing, heating and air conditioning technology, or a profession requiring a comparable level of knowledge [specialist].
The following must be observed during installation and commissioning:
- relevant local and national regulations
- accident prevention regulations of the professional association
- instructions and safety instructions mentioned in these instructions.

CAUTION
Personal injury and damage to property!
The product must only be used in heating circuits filled with heating water according to VDI 2035 / Ö-Norm H 5195-1. The product must not be used in domestic water applications.

NOTICE
Material damage due to mineral oils!
Mineral oil products cause lasting damage to seals made of EPDM, whereby the sealant properties get lost. We do not assume liability nor provide warranty for damage to property resulting from sealants damaged in this way.
- It is imperative to avoid that the EPDM sealing elements of the unit get in contact with substances containing mineral oils.
- Use a lubricant based on silicone or polyalkylene and free from mineral oils, such as Unisilikon L250L and Syntheso Glep 1 of the Klüber company or a silicone spray.