Solex|SolarBloC®

Solar

thermal

systems

SolexMega TW up to 200 m²

Field of application: for charging buffer storage tanks
Application range: up to 200 m² collector surface
with heat quantity measurement according to the BAFA promotion directive for solar thermal systems

The CE-conformity of the installation has been certified according to DIN EN 60335.

SKU
6097465x
Prices are only visible for registered users.

Our offer is exclusively aimed at corporate clients.

Manufacturer:
PAW GmbH & Co. KG
Böcklerstr. 11 31789 Hameln
Germany
info@paw.eu
Operating data
Max. operating pressure primary: 6 bar
Max. operating pressure secondary: 10 bar
Max. operating temperature primary: 120 °C
Max. operating temperature secondary: 95 °C
Equipment
Controller: SC5.14
Check valves: primary: 2 x 250 mm wc / secondary: 1 x 150 mm wc
Pressure gauge: 0-6 bar, resistant to high temperatures
Shut-off valves: Ball valves and piston valves
Sensors: 2 x Pt1000 (integrated) / 2 x Pt1000 (enclosed)
Heat exchanger: XB37M-1, 2x 50 plates
Safety valve: primary: 6 bar / secondary: 10 bar
FlowRotor: 5-100 l/min
Airstop: yes
Number of check valves: 3
Dimensions
Height: 1654 mm
Width: 710 mm
Nominal diameter: DN 32 (1¼")
Depth: 920 mm
Installation length: 1175 mm
Centre distance: 158 mm
Connection primary: 1½" int. thread
Connection secondary: 1½“ ext. thread
Materials
Valves and fittings: Brass
Gaskets: EPDM / AFM34
Insulation: EPP
Piping: Stainless steel
Check valves: Brass
Heat exchanger: Solder: copper,Plates + connecting pieces: stainless steel
Design data
Operating mode LowFlow: 15 l/(m²xh)
Operating mode HighFlow: 25 l/(m²xh)
Collector surface LowFlow: 200 m²
Collector surface HighFlow: 160 m²
Output LowFlow: 100 kW
Temperature difference LowFlow: 33 K
Temperature difference HighFlow: 12 K
Boundary conditions: Irradiation = 800 W/m²; efficiency ᵑ0.05 = 65%
The compact and completely premounted solar transfer station is completely insulated and equipped with a generously dimensioned stainless steel plate heat exchanger and with a preset and prewired controller.For a simple and quick installation as well as a safe commissioning.

Primary connections: 1½" internal thread, secondary connections: 1½" external thread

All fluid-carrying parts made of brass or stainless steel, fully assembled - self-sealing or flat gaskets

Floor-standing station, premounted in steel rack,
simple and quick installation and connection

Full port ball valves on primary side, with large levers for easy handling, visible closing position
full port piston valves on secondary side

Check valves in the primary flow and return ball valve, can be opened, 200 mm wc, especially for solar systems, prevent unwanted circulation

Solar circuit with large ball valve handles
easy handling, visible closing position, with integrated full metal thermometer 0-160 °C, can be pulled off, with immersion sleeve integrated in the ball valve, piston valves in the secondary circuit

Airstop in the flow line
for permanent deaeration of the solar fluid and for controlled venting of the installation

With high-efficiency pumps by Grundfos (PWM for speed control), premounted and prewired, adapted to the performance of the transfer station, pumps can be isolated completely, no draining during servicing

FlowRotor, flow meter on primary side for speed control of the secondary pump, depending on the performance and heat quantity balancing (primary)

Flush and fill unit integrated
two fill and drain valves in the flow and return permit filling and flushing the primary circuit

Solar safety group
Solar pressure relief valve 6 bars, pressure gauge resistant to high temperatures 0-6 bars with valve, flat sealing connection for a diaphragm expansion tank, secondary side with pressure relief valve, 10 bars

Compact design insulation with optimised function
made of durable elastic EPP, 100 % insulated valves and fittings - excellent ventilation and cooling of the pumps, minimal heat losses

Safety instructions
The installation and commissioning as well as the connection of electrical components require technical knowledge commensurate with a recognised vocational qualification as a fitter for plumbing, heating and air conditioning technology, or a profession requiring a comparable level of knowledge [specialist].
The following must be observed during installation and commissioning:
- relevant local and national regulations
- accident prevention regulations of the professional association
- instructions and safety instructions mentioned in these instructions.

WARNING
Personal injury due to contaminated domestic water!
Heating water contains harmful substances that must not be washed into the domestic hot water circuit.
If the station has been used to charge a buffer tank, there is still heating water in the valves and fittings and in the pump of the secondary circuit, even after draining. The heating water cannot be completely removed.
-The station must not be connected to a domestic hot water circuit any more.

WARNING
Danger of scalding due to the escape of hot fluids!
With pressure relief valves, there is a risk of scalding due to the escape of vapour or hot fluid. During installation, check the local conditions and check whether a discharge line must be connected to the safety group.
- Observe the instructions regarding the pressure relief valve.
- The pressures for the expansion tank calculated by the plant designer and the operating pressure of the installation must be set.

CAUTION
Personal injury and material damage due to overpressure!
Closing both ball valves in the primary circuit will separate the safety group from the heat exchanger. A rise in temperature in the storage tank may result in high pressures, which may lead to personal injury and material damage!
- Only close the ball valves for service and maintenance.
- When closing the ball valves in case of servicing, also put the pumps out of operation and close the ball valves / piston valves of the secondary circuit.

CAUTION
Risk of burns!
Valves, fittings and pump may heat up to more than 100 °C during operation.
The insulating shell must remain closed during operation.

NOTICE
Material damage due to mineral oils!
Mineral oil products cause lasting damage to seals made of EPDM, whereby the sealant properties get lost. We do not assume liability nor provide warranty for damage to property resulting from sealants damaged in this way.
- It is imperative to avoid that the EPDM sealing elements of the unit get in contact with substances containing mineral oils.
- Use a lubricant based on silicone or polyalkylene and free from mineral oils, such as Unisilikon L250L and Syntheso Glep 1 of the Klüber company or a silicone spray.