• Best quality
  • Quick assembly
  • Longevity

HeatBloC®

Heating

technology

Return flow temperature maintenance with thermal control valve (45 °C) - DN 20 (¾")

Return flow temperature maintenance - DN 20 (¾")
with thermal control valve (45 °C)
Opening temperature: 45 °C
Field of application: for heating systems with return flow temperature maintenance
for solid fuel boilers, wood-fired and stove heating systems

SKU
960250x
Prices are only visible for registered users.

Our offer is exclusively aimed at corporate clients.

Manufacturer:
PAW GmbH & Co. KG
Böcklerstr. 11 31789 Hameln
Germany
info@paw.eu
Operating data
Max. operating temperature: 110 °C
Dial thermometer: 0 - 120 °C
Output: 11 kW
Max. operating pressure: 6 bar
Temperature difference: 10 K
Kvs value: 4.7
Flow rate: 950 l/h
Equipment
Dial thermometer: 0 - 120 °C
Shut-off valves: Ball valves with handle
Thermal control valve: Opening temperature: 45 °C
Equipment: red and blue dial thermometer, integrated into black plastic handles (0-120°C)
Dimensions
Nominal diameter: DN 20 (¾")
Installation length: 336 mm
Installation height: 112 mm
Connection generator: ¾" int. thread
Connection consumer: ¾" int. thread
Materials
Valves and fittings: Brass
Gaskets: EPDM
Insulation: EPP
Pump fitting group, can be isolated, consisting of:

- Pump
- Control valve with opening temperature 50/60 °C (± 3 K)
- 1 thermometer ball valve with red thermometer integrated in the handle, can be pulled off
- 2 thermometer ball valves with blue thermometers integrated in the handles, can be pulled off

Connections:

Thermal control valve with automatic bypass
1. The thermal valve shuts off the connection to the buffer tank, as long as the water in the boiler circuit is colder than the opening temperature of the thermal control valve. The pump circulates the water in the boiler circuit through the bypass. The small quantity of water in the boiler circuit can now heat up quickly.
2. When the boiler circuit reaches the opening temperature of the control valve, the valve reduces the bypass flow rate and opens the buffer tank circuit. The cold water from the buffer tank return is mixed with the hot boiler circuit water in the control valve. This leads to an increase of the return temperature in the boiler circuit to the desired level and avoids condensation in the boiler.
3. When the buffer tank return temperature is higher than the opening temperature, the control valve completely shuts off the bypass. Thus, the water from the buffer tank flows directly into the boiler circuit.

Please note:
If the boiler output is controlled by the boiler temperature, the boiler should heat up 20 °C above the opening temperature of the return flow temperature maintenance. Otherwise the boiler might reduce the output even before the thermal control valve is completely open.

Mounting version:
Separate assembly of the group of fittings in the flow and return.
This version permits an easy isolation of the heat generator without further shut-off valves. Consider the position of the safety group before mounting.

Additionally required:
1 x gasket, 1 x fitting and 1 x pump fitting

Safety instructions
The installation and commissioning as well as the connection of electrical components require technical knowledge commensurate with a recognised vocational qualification as a fitter for plumbing, heating and air conditioning technology, or a profession requiring a comparable level of knowledge [specialist].
The following must be observed during installation and commissioning:
- relevant local and national regulations
- accident prevention regulations of the professional association
- instructions and safety instructions mentioned in these instructions.

CAUTION
Personal injury and damage to property!
The product must only be used in heating circuits filled with heating water according to VDI 2035 / Ö-Norm H 5195-1. The product must not be used in domestic water applications.

NOTICE
Material damage due to mineral oils!
Mineral oil products cause lasting damage to seals made of EPDM, whereby the sealant properties get lost. We do not assume liability nor provide warranty for damage to property resulting from sealants damaged in this way.
- It is imperative to avoid that the EPDM sealing elements of the unit get in contact with substances containing mineral oils.
- Use a lubricant based on silicone or polyalkylene and free from mineral oils, such as Unisilikon L250L and Syntheso Glep 1 of the Klüber company or a silicone spray.